This paper dealt with the fabrication of a partial discharge (PD) analyzer for insulation diagnosis of power facilities like transformers, cables and gas-insulated switchgears. An analytic algorithm for the phase (φ), the magnitude (q), and the pulse count (n) of PD pulse was designed and a time-frequency (TF) map algorithm was applied in the system to eliminate noises by analyzing the time and the frequency component of signals. All the algorithms were operated by a LabView graphical program. The detection circuit consists of a coupling capacitor, a detection impedance, and a low noise amplifier. A plane-plane and a point-plane electrode system were fabricated to simulate different types of insulation defects. In the experiment, we could easily understand the characteristics of PD pulses using the prototype PD analyzer.