In this study, to develop angle ring pressboards for high voltage transformers, the radius and thickness are modified under the conditions of temperature and humidity. In particular, a pressboard with a thickness of 6 mm and a radius at the angled part were investigated based on the simulation of the principal stress from the angled optimization profile shape. As a result, by the appropriate application of a higher temperature, the solid insulation can be improved to reduce the moisture content for an optimized profile angle of a high voltage transformer. This also results in the improvement of the safety factor by 25%. It is determined that the electrical insulation properties of pressboards in high voltage transformers can be enhanced by improving their properties.
Some insulating materials are tested and analyzed with variables to obtain the reliable pressboard which is located to core and coil of high voltage transformer. The high voltage transformer is used in electrical power system and operating reliability. Optimization possibility of pressboard shape including electrical insulation performance could be achieved by analysis simulation. Using insulating pressboard, which is made by mold applied eddy current loss, it could be measured the influences of moisture content for electrical properties. As a result, it is to contribute to improve the performance and ensure the reliability of the pressboard by investigating electrical strength according to the variation oil temperature. In addition pressboard thickness is important design factor to ensure electrical strength in high voltage transformer.