This paper proposes an easy algorithm for finding tapped-delay-line (TDL) filter coefficients in an adaptive filter algorithm using orthogonal input signals. The proposed algorithm can be used to obtain the coefficients and errors of a TDL filter without using an inverse orthogonalization process for the orthogonal input signals. The form of the proposed algorithm in this paper has the advantages of being easy to use and similar to the familiar recursive least-squares (RLS) algorithm. In order to evaluate the proposed algorithm, system identification simulation of the 11th-order finite-impulse-response (FIR) filter was performed. It is shown that the convergence characteristics of the learning curve and the tracking ability of the coefficient vectors are similar to those of the conventional RLS analysis. Also, the derived equations and computer simulation results ensure that the proposed algorithm can be used in a similar manner to the Levinson-Durbin algorithm.
Most series arcs lead to electrical fires that cannot be interrupted by circuit breakers, because the arc’s current is outside the breaker’s operating range. In this paper, experiments were conducted on the detection and identification of series arcs to prevent electrical fires. Plugs and outlets specified in KS C 8305 were deteriorated to replicate arc faults commonly found in fields. The characteristics of series arcs resulting from various types of loose connections were determined by analyzing the frequency spectra and phase distributions of detected arc pulses. The results showed that the simulated arc defects used in this study were more similar to actual arc phenomena than the existing arc generator specified in UL 1699. In addition, loose connections, such as wire-wire, terminal-wire, and outlet-plug, can be identified by phases of 0°, 180° and 360°, respectively. These phases can be detected by a band pass filter with a frequency range of 5~10 MHz, which can be used as the trip signal for circuit breakers.
This paper dealt with a defect identification algorithm which is based on single partial discharge (PD) pulse analysis in gas insulated structure. Four types of electrode systems such as a needle-plane, a plane-needle, a free particle and a crack inside spacer were fabricated to simulate defects in gas insulated switchgear (GIS). We measured single PD pulse by an oscilloscope with a sampling rate of 5 GS/s and a frequency bandwidth of 1 GHz. Data aquisition and signal processing were controlled by a LabVIEW program. Physical shapes of PD pulses were compared with kurtosis, skewness and time-based parameters as rising time, falling time and pulse-width. These parameters were analysed by an algorithm with a back propagation algorithm (BPA). By applying the algorithm, the identification rate was 97% for the needle-plane electrode, 96% for the plane-needle electrode, 91% for the free particle and 93% for the crack inside spacer. The results verified that the algorithm could identify the type of defects in GIS.