Some insulating materials are organized and analyzed with variables to obtain the optimized profile of encapsulated three phase of epoxy barrier which is applied to gas compartment and supporting conductors for high voltage GIS (gas insulated switchgear). The high voltage GIS is used in electrical power system and operating reliability. In this paper, optimization possibility of barrier shape including both electrical insulation performance and mechanical strength, premised on that condition minimizing volume and light weight should be kept for high voltage GIS, could be achieved by analysis simulation. As a result, filling material which is lower permittivity such as SiO2 instead of Al2O3 properly to the epoxy material, can be improved to increase the electrical insulation performance and mechanical strength for an optimized profile barrier of a high voltage GIS.
In this paper, in order to avoid equipment malfunction due to electromagnetic waves, which can occur when high-voltage live line diagnostic device fabrication, the enclosure structure of the diagnostic device with power lines that can minimize the EMI (electromagnetic interference) was modeled using the FEM (finite element method). Simulation examined the strength of the electric field in the required thickness, material and regions where there is a control board while changing the curvature radius of the corner making the enclosure, and By applying a mechanical design and simulation results that occur during the actual production has been designed for the final design. Most of the simulation results for the electric field is concentrated in the final model, the inner edge of the enclosure could be confirmed that the stable structure.