This paper dealt with the measurement and analysis of partial discharge (PD) under high voltage direct current (HVDC) in SF6 gas. Electrode systems such as a protrusion on conductor (POC), a protrusion on enclosure (POE), a crack on epoxy plate and a free particle (FP) were fabricated to simulate the insulation defects. The analysis system was designed with a Time-Frequency (T-F) map algorithm programed based on Lab VIEW. This can arrange the acquired PD pulses into frequency and time domain. A HVDC power source is composed of a transformer (220 V/50 kV), a diode (100 kV) and a capacitor (50 kV, 0.5 μF). The gap between the electrodes is 3 mm, and the SF6 gas was set at 5 bar. PD pulses were detected by a 50 Ω non-inductive resistor. In the analysis, PD pulses were distributed below 0.5 MHz and 20 ns ∼ 35 ns for the POC, 0.7 MHz ∼ 1.7 MHz, below 0.6 MHz and 10 ns ∼ 40 ns and 60 ns ∼125 ns for the POE, below 0.1 MHz and 135 ns ∼ 215 ns for the crack, and below 1.6 MHz and 250 ns for the FP.
Citations
Citations to this article as recorded by
Identification of Partial Discharge Defect Detection in Cast-Resin Power Transformers Using Back-Propagation Algorithm Sung-Wook Kim Journal of information and communication convergence engineering.2024; 22(3): 231. CrossRef