Design and Fabrication of Rogowski-type Partial Discharge Sensor for Insulation Diagnosis of Cast-Resin Transformers
Gyeong-yeol Lee, Sung-wook Kim, Gyung-suk Kil
J Korean Inst Electr Electron Mater Eng 2022;35(6):594-602.   Published online November 1, 2022
DOI: https://doi.org/10.4313/JKEM.2022.35.6.8
Cast-resin transformers are widely installed in various electrical power systems because of their low operating cost and low influence on external environmental factors. However, when they have an internal defect during the manufacturing process or operation, a partial discharge (PD) occurs, and eventually destroys the insulation. In this paper, a Rogowski-type PD sensor was studied to replace commercial PD sensors used for the insulation diagnosis of power apparatus. The proposed PD sensor was manufactured with four different types of PCB-based winding structures, and it was analyzed in terms of the detection characteristics for standard calibration pulses and the changes of the output voltage according to the distance. The output increased linearly in accordance with the applied discharge amount. It was confirmed that the hexagon structure sensor had the highest sensitivity, because the winding cross-sectional area of the sensor was larger than others. In addition, as the distance from the defect increased, the output voltage of the sensors decreased by 7.32% on average. It was also confirmed that the attenuation rate according to the distance decreased as the input discharge amount increased. For the application of this new type sensor, PD electrode system was designed to simulate the void defect. Waveforms and PRPD patterns measured by the proposed PD sensors at DIV and 120% of DIV were the same as the results measured by MPD 600 based on IEC 60270. The proposed PD sensors can be installed on the inner wall of the transformer tank by coating its surfaces with a non-conductive material; therefore, it is possible to detect internal defects more effectively at a closer distance from the defect than the conventional sensors.
  • 73 View
  • 0 Download
Regular Paper : Detection Technique of Partial Discharge by a Capacitive Probe in Cast-resin Transformers
Kwang Seok Jung, Dae Won Park, Hyeon Kyu Cha, Sang Wook Cha, Gyung Suk Kil
J Korean Inst Electr Electron Mater Eng 2011;24(4):319-324.   Published online April 1, 2011
DOI: https://doi.org/10.4313/JKEM.2011.24.4.319
This paper dealt with a partial discharge (PD) detection method for insulation diagnosis in cast-resin transformers. To detect PD pulse, a planar-capacitive probe was designed and fabricated. The probe has no insulation problem and can be installed on cast-resin transformers even in operation since it does not connect with high voltage conductor. The PD measurement system consists of the capacitive probe, a coupling network of 100 [kHz] low-cutoff frequency, and an amplifier with a gain of 40 [dB] and a frequency bandwidth of 500 [Hz]∼45 [MHz]. A plane-needle and a plane-plane electrode system were fabricated to simulate insulation defects in a cast-resin transformer. Sensitivity of the PD measurement system, which is evaluated by a standard calibrator was 0.35 [mV/pC] for positive and 0.45 [mV/pC] for negative, respectively. The PD detection by the capacitive probe was less sensitive than that by a coupling capacitor according to IEC 60270, but we could analyze the magnitude and the phase distribution of PD pulse.

Citations

Citations to this article as recorded by  
  • Machine Learning-Based Partial Discharge Recognition in Cast-resin transformers Using Phase-Synchronized Partial Discharge Detection Technique
    Gyeong-Yeol Lee, Gyung-Suk Kil
    Journal of Electrical Engineering & Technology.2026; 21(6): 5147.     CrossRef
  • 90 View
  • 0 Download
  • 1 Crossref
A Study on PD Detection Methods for Cast-resin Dry-type Transformers
Chan Yong Park, Dae Won Park, Jae Sung Choi, Gyung Suk Kil
J Korean Inst Electr Electron Mater Eng 2009;22(9):786-791.   Published online September 1, 2009
DOI: https://doi.org/10.4313/JKEM.2009.22.9.786

Citations

Citations to this article as recorded by  
  • Nb-embedded Janus WSSe monolayer as a resistive or Schottky gas sensor upon CO, HCHO and C2H3Cl in dry transformers: a first-principles investigation
    Dan He, Guangming Li, Wen Cao, Hao Cui
    Physics Letters A.2025; 553: 130669.     CrossRef
  • DFT simulations of Al-doped MoTe 2 monolayer as an HCHO and C 2 H 3 Cl gas sensor for status evaluation of a dry-type reactor in the HVDC converter station
    Pei Guo, Chao Xiao, Meng Yao, Yao Liu, Jing Hu, Jian Hu, Tai Li
    Molecular Physics.2025;[Epub]     CrossRef
  • Fault signature gas sensing by the Ni-dispersed SnS 2 monolayer for operation status evaluation of dry-type transformer: a first-principles study
    Zhigang Chen, Chaoliang Qi, Xin Chen, YuZhe Bao, Yanan Yang, Fan Zhou
    Molecular Physics.2025;[Epub]     CrossRef
  • Single Ni Atom-Dispersed WSe2 Monolayer for Sensing Typical Fault Gases in Dry-Type Transformers: A First-Principles Study
    Yan Liu, Jianben Liu, Zhuo Wei, Tian Yuan, Hao Cui
    ACS Omega.2023; 8(49): 47067.     CrossRef
  • Implementation of Prediction Program for Deterioration Judgment on Substation Power Systems in Urban Railway
    Ho-Sung Jung, Young Park, Hyun-Il Kang
    The Transactions of The Korean Institute of Electrical Engineers.2013; 62(6): 881.     CrossRef
  • 77 View
  • 0 Download
  • 5 Crossref